Huawei LUNA2000 Series are an integrated range of smart Energy Storage Systems (ESS) designed for Commercial & Industrial (C&I) applications. These systems store energy—usually from solar PV installations—and manage its use for self-consumption, backup and energy cost optimization. This system is an ideal choice for facilities seeking to reduce energy costs, manage peak loads, and improve energy independence. With a compatible communication protocol, the LUNA2000 ESS series integrates seamlessly with energy management systems, supporting smart control and real-time monitoring. Particular features include:-
- Modular Design: Scalable battery units that can be expanded as energy needs grow.
- Advanced Cooling: hybrid liquid + air cooling for C&I models improving efficiency and safety.
- High Round-Trip Efficiency: Up to 91.3% for minimal energy loss.
- Enhanced Safety: Multi-level protection, including cell-level monitoring, fire prevention, and C2C (cell-to-consumption) safety architecture.
- Smart Management: Integration with Huawei's Fusion Solar Smart PV platform for real-time monitoring, energy management, and remote diagnostics.
- Flexible Integration: Supports both on-grid and hybrid installations and integrates with Huawei's inverters and third-party EMS systems.
Use Case Scenarios:
- Commercial buildings and industrial facilities
- Microgrids and off-grid power systems
- Backup for critical infrastructure (e.g., hospitals, data centers, banks, institutions)
TECHNICAL SPECIFICATIONS
Enclosure Class: IP55
Operating Temp Range: -30°C to 55°C
| Energy Storage System Parameters |
| Model |
LUNA2000-107-1S11 |
LUNA2000-161-2S11 |
LUNA2000-215-2S10 |
| Rated Capapcity, kWh |
107 |
161 |
215 |
| Maximum Cycle Rate, C |
1 |
0.67 |
0.5 |
| Recommended PV Array, kWp |
57.5 |
69 |
115 |
| Maximum PV Array, kWp* |
215 |
322.6 |
430 |
| Compatible Inverters |
SUN2000-30-50KTL-M3 |
SUN2000-100-115KTL-M1/M2 |
SUN2000-150K-MG0 |
| Maximum Cycle Efficiency, % |
86 |
88 |
91.3 |
| Dimensions (WxDxH), mm |
1150x1800x2100 |
| Weight, kg |
2000 |
2400 |
2800 |
| Battery Parameters (DC) |
| Rated Battery Capacity, Ah |
280 |
| Number of Battery Packs |
2 |
3 |
4 |
| Operating Voltage Range, V |
324-432 |
486-648 |
648-864 |
| Rated DC Current, A |
280 |
187 |
140 |
| PCS Parameters (AC) |
| PCS Model Type |
CS2000-108K-MB1 |
| Rated Output Power, kW |
108 |
| Rated AC Current, A |
155.9 |
| AC Voltage & Frequency |
380/400/415/420/440/480 V (3P4W), 50/60Hz |
| Adjustable Power Factor Range |
-1 ... +1 |
Notes: The ratio of PV and BESS should always be less than 2:1 in the switchover and pure off-grid scenarios • The actual PV Array in kWp must be designed based on the loads to be powered